14-4C Solid Copper AC Lite Interlocked Galvanized THHN Insulation Aluminum Armored Cable
Allowable Ampacity for 14-4C Solid Copper AC Lite Interlocked Galvanized THHN Insulation Aluminum Armored Cable 100 Amps
Armored Cable (AC Cable), also known as BX Electrical Cable, is a flexible conduit alternative to pipe-and-wire installations, manufactured to UL 4 standards. It features a 16 AWG bare aluminum bond wire used with the armor as the grounding path. AC Cable is approved for various applications under NEC Code and is limited to four phase conductors in sizes ranging from 14 AWG to 1 AWG. Unlike other cable types that use polypropylene wraps or direct extrusion over conductors, AC Cable incorporates a paper wrap.
Applications:
Designed for commercial, industrial, and multi-residential branch circuits and feeder wiring, supporting power, lighting, control, and signal circuits. Suitable for exposed or concealed installations, including surface mounting, embedding in plaster finishes on brick or masonry (excluding wet or damp locations), fishing through air voids in masonry block or tile walls, under raised floors, above suspended ceilings, and within other environmental air-handling spaces. Features galvanized aluminum armor for durability.
Also Known as:
AC Cable, AC Lite Cable, Interlocked Galvanized, Interlocked Armored, Interlocked Aluminum, Armored Cable, Aluminum Cable, Galvanized Interlocking, Aluminum Strip Cable, 120/208V Cable, 480Y/277V Cable
Construction:
• Armor: Interlocking Aluminum Strip (silver or black striped)
• Conductors: Solid Copper
• Conductor Insulation: THHN
• Conductor Insulation Covering: Moisture resistant Fire Retardant Paper Wrap
• Grounding: 16AWG integral Bond Wire/combination
• Neutral Conductor: White 120/208V
• Maximum Voltage Rating: 600V
• Maximum Temperature Rating: 90°C (Dry)
Features & Benefits:
• Interlocking galvanized
• Integral bond wire/armor equipment ground fault path
• UL classified for through-wall penetrations
• Aluminum armored cables are RoHS Compliant
• Made in USA of US and/or imported materials
References & Ratings:
• UL 4, 83, 1479, 1581, 2556, File Reference E7330
• NEC 250.118(8), 300.22(C), 392, 320, 645
• Federal Specification A-A–59544 (formerly J-C–30B)
• Cable Tray Rated, install per NEC
• UL Classified 1, 2, and 3 hour through (Fire) penetration product, R–14141
• Environmental Air-Handling Space Installation per NEC 300.22(C)
• Aluminum armored cables are RoHS Compliant
• Meets all applicable OSHA and HUD Requirements
• Made in USA of US and/or imported materials
Specification:
• Phase AWG Size: 14
• Number of Conductors: 4
• Armor MIN. O.D: 0.486 Inch
• Weight 1000ft: 120 Lbs
• (Black / Red / Blue / White) 250′ Coil Code: 2703-42-00
• (Black / Red / Blue / White) 1000′ Reel Code: 2703-60-00