2/0 AWG 1C rm/16 Stranded Bare Copper Tape Shielded XLPE PE N2XS2Y 12/20KV Medium Voltage Cable
[pdf] [/pdf]
2/0 AWG 1C rm/16 Stranded Bare Copper Tape Shielded XLPE PE N2XS2Y 12/20KV Medium Voltage Cable
Allowable Ampacity for 2/0 AWG 1C rm/16 Stranded Bare Copper Tape Shielded XLPE PE N2XS2Y 12/20KV Medium Voltage Cable: 100 Amps
About:
This cable specification denotes a medium voltage cable with a 2/0 AWG single conductor that uses an rm/16 stranding pattern for the stranded bare copper. It incorporates tape shielding and employs cross-linked polyethylene (XLPE) for insulation with a polyethylene (PE) outer jacket. The cable is rated for 12/20KV, indicating its suitability for higher medium voltage levels compared to the 6/10KV variant.
Also Known As:
• “2/0 AWG 1C” indicates a 2/0-gauge size with one conductor.
• “rm/16” details the stranding structure of the conductor.
• “Stranded Bare Copper” identifies the conductor material.
• “Tape Shielded” describes the inclusion of a shielding layer.
• “XLPE PE” refers to the insulation and jacketing materials used.
• The voltage rating “12/20KV” specifies its operational voltage capacity.
Application:
Suitable for installation mostly for power supply stations, in indoors and in cable ducts, outdoors, underground, and in water as well as for installation on cable trays for industries, switch-boards and power stations. Due to the good laying characteristics, this can also be laid easily in difficult line guideways. See DIN VDE 0298 part 1
Standards:
• Adheres to IEC (International Electrotechnical Commission) standards applicable to medium voltage power cables.
• Meets relevant national and international standards ensuring safety, reliability, and performance in medium voltage applications.
Construction:
• Conductor: Stranded red copper conductor Cl.2, acc.to IEC 60228
• Inner Semi-Conductive Layer: Extruded Semi-Conducting Compound
• Insulation: XLPE, type DIX 8
• Outer Semi-Conductive Layer: Extruded Semi-Conducting Compound
• Screen: Red copper wires and one or two copper tape(s) applied helically, if necessary
• Outer Sheath: Black (RAL 9005), PE type DMP2
Features:
• Water resistant
• UV resistant on request
• re: circular solid conductor
• rm: circular stranded conductor
• sm: sector-shaped stranded conductor
• se: sector-shaped solid conductor
Specifications:
• No. of cores x cross section n x mm²: 1×70 rm/16
• AWG no.: 2/0
• Outer-Ø ca.mm ± 10%: 32,5
• Copper Weight kg/km: 854
• Nominal Voltage: Uo/U 6/10 kV, Uo/U 12/20 kV, Uo/U 18/30 kV
• Test Voltage: Uo/U 6/10 kV = 17 kV, Uo/U 12/20 kV= 29 kV, Uo/U 18/30 kV = 45 kV
• Max. Operating Voltage: Uo/U 6/10 kV = Um 12 kV, Uo/U 12/20 kV = Um 24 kV, Uo/U 18/30 kV = Um 36 kV
• Temperature range: – 20° C up to + 70° C
• Cable Weight approx. kg/km: 1410
• Part Number: 48200U7L010M66