2/0 AWG 3C MV-105 AIA Power Cable NL-EPR 133/100% Insulation PVC Yellow Jacket 5/8kV
[pdf] [/pdf]
2/0 AWG 3C MV-105 AIA Power Cable NL-EPR 133/100% Insulation PVC Yellow Jacket 5/8kV
Application:
Type MV-105 Three Conductor Aluminum, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket. Silicone Free
Also Known As:
2/0 AWG 3C MV-105 Cable, NL-EPR Cable, 2/0 AWG 3C Interlocked Armor Cable, Silicone Free Cable, Armor Cable, 2/0 AWG 3C MV-105 AIA Cable, Power Cable.
Standards:
• ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
• ASTM B836 Compact Rounded Stranded Aluminum Conductors
• UL 1072 Medium-Voltage Power Cables
• UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 – 46kV
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
Features:
• Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired.
• These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with “LTGG” when CSA listed or dual UL/CSA listed.
• For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Construction:
• Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
• Conductor Shield: Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
• Insulation: 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
• Insulation Shield: Strippable semi-conducting cross-linked copolymer
• Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
• Grounding Conductor: Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
• Filler: Wax paper filler
• Binder: Polypropylene tape
• Armor: Aluminum Interlocked Armor (AIA)
• Overall Jacket: Polyvinyl Chloride (PVC)
Specifications:
• Size: 2/0 AWG
• Conductor Number: 3
• Number of Strands: 19
• Diameter Over Conductor (In): 0.376
• Diameter Over Insulation (In): 0.644
• Diameter Over Insulation Shield (In): 0.704
• Ground No. x AWG: 1×4
• Diameter Over Armor (inch): 1.885
• Jacket Thickness (Mils): 60
• Approx. OD (In): 2.005
• Approx. Weight (Lbs/1000′): 1721
• Max Pull Tension lb: 2395
• Min. Bend Radius (In): 14.0
• Allowable Ampacity In Duct 90/105°C (Amp): 140/150
• Allowable Ampacity In Air 90/105°C (Amp): 145/160