2 x 4 mm² BFOU P5/P12 Power and Control 0.6/1KV Fire Resistant Cable 02C004-Z

2 x 4 mm² BFOU P5/P12 Power and Control 0.6/1KV Fire Resistant Cable 02C004-Z

Allowable Ampacity for 2 x 4 mm² BFOU P5/P12 Power and Control 0.6/1KV Fire Resistant Cable 02C004-Z: 100 Amps

Applications:

Mud resistant cables suitable for control, lighting and power systems

Also Known As:

BFOU P5/P12, Power Cable, Control Cable, Offshore Cable, Fire Resistant Cable, Halogen free Cable, Marine Cable, Marine Shipyard Cable

Construction:

• Conductors: Tinned annealed stranded copper IEC 60228 class 2

• Insulation: – MGT (Mica glass tape), halogen free EPR (Ethylene Propylene Rubber)
                      – Mica tape + Halogen free EPR compound
                      – Separator (if necessary) Halogen free tape

• Screen: TCWB (Tinned copper wire braid)

• Sheath/Jacket: Type: SHF, thermoset dual compound, halogen free and mud resistant

• Bedding: Halogen free compound

• Armour: Tinned copper wire braid according to IEC 60092-352

• Outer Sheath: SHF2 MUD thermoset dual compound Halogen free & MUD resistant

• Sheath Colours: Black

• Voltage: 600/1000v

• Operating Temperature: Maximum 90°C

• Cold Bend/Impact: CSA 22.2 NO. 0.3 (-40°C)

Core Identification:

• Single Core: off-white
• 2 Core: off-white & black
• 3 Core: off-white, black & red
• 4 Core: off-white, black, red & blue. Including green / yellow core options

Sheath Marking:

• BFOU P5/P12 0.6/1 kV n x s / braid
• NEK 606 IEC 60331-31 QA ref Metric marking

Standards:

• IEC60092-353: electrical installation in ships, power cables
• NEK606: cables for offshore installation halogen-free or mud-resistant
• IEC60092.375: shipboard telecommunications cable
• IEC60331: fire resistant
• IEC60332: flame retardant
• IEC61031-1.2: smoke denisty
• IEC60754-1: halogen free properties
• IEC60228: electical conductor

Type Approvals:

• ABS, DNV Lloyd’s Register of Shipping

Product Table:

• Design and Construction: IEC 60092-353
• Operating Temperature: 90°C
• Nominal Voltage Uo/U: 0.6/1 kV
• Flame Retardancy: IEC 60332-1, IEC 60332-3-22
• Flame Resistance: IEC 60331-31
• Corrosivity: IEC 60754-1, IEC 60754-2
• Smoke Density: IEC 61034-2
• MUD Resistance: NEK 606:2004
• On request: Cold Bend and impact (-40°C) CSA C22.2 No 38-95

Specification:

Construction: 2 x 4/7 mm2
Insulation Thickness: 1.0 mm
Under Armour Diameter: 12.6 mm
Outer Sheath Thickness: 1.5 mm
Overall Diameter (approx): 17 mm
Bending Radius: 80 mm
Conductor Resistance at 20ºC: 4.700 Ω/km
Current Rating at 45ºC: 37 A
Short Circuit Rating: 0.58 kA
• Weight (approx): 0.332 Lbs/Ft