20S16 Cable Gland PX2K Globally Metal Armour Clamping CMP SOLO LSF Barrier Explosive Atmosphere
20S16 Cable Gland PX2K Globally Metal Armour Clamping CMP SOLO LSF Barrier Explosive Atmosphere
Allowable Ampacity for 20S16 Cable Gland PX2K Globally Metal Armour Clamping CMP SOLO LSF Barrier Explosive Atmosphere: 100 Amps
Also Known As:
Cable Gland, PX2K Cable Gland, Globally Gland, Armour Clamping Gland, CMP SOLO Gland, LSF Halogen Free Gland, Barrier Cable Gland
Construction:
• Design Specification: BS 6121:Part 1:1989, IEC 62444, EN 62444
• Mechanical Classifications *: Impact = Level 8, Retention = Class D
• Enclosure Protection: IK10 to IEC 62262 (20 Joules) Brass & Stainless Steel Only
• Electrical Classifications *: Category B (Category A When Used With Braid, Tape or Pliable Wire Armour Cables)
• ATEX Certificate: SIRA13ATEX1072X, SIRA13ATEX4078X
• Code of Protection: II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb
• Compliance Standards: EN 60079-0,1,7,15,31
• IECEx Certificate: IECEx SIR 13.0027X, IECEx SIM 14.0008X
• Code of Protection: Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
• Compliance Standards: IEC 60079-0,1,7,15,31
• cCSAus Certificate (20s16 – 100): 2288626
• CSAus Code of Protection***: Class I, Div. 1, 2 Groups A, B, C and D; Class II, Div. 1, 2 Groups E, F and G; Class III, Div. 1, 2; Type 4X: Oil Resistant II: Class I, Zone 1 AEx d IIC Gb, AEx e IIC Gb, Class I, Zone 2 AEx nR IIC Gc, Class I, Zone 20 AEx ta IIIC Da
• cCSA Code of Protection***: Class I, Div. 1, 2 Groups A, B, C and D; Class II, Div. 1, 2 Groups E, F and G; Class III, Div. 1, 2; Type 4X: Oil Resistant II: Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
• Compliance Standards: CAN/CSA-C22.2 No 0,18,25,30,94,174, CAN/CSA-E60079-0,1,7,15,31 CAN/CSA-E61241-1-1 Part 1-1, ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079
• UL Certificate (20s16 – 100): E201187, E161256C
• Code of Protection: Class I Div 1,2, Groups A,B,C,D, Class II Div 1,2, Groups E,F,G
• Compliance Standards: UL 2225, CSA C22.2 No 174, UL 514B, CSA C22.2 No 18, CSA C22.2 No 30
• UkrSEPRO: UA.TR.047.C.0644-15
• EAC Certificate: C-GB.AA87.B.00487
• KCC Certificate: 14-GA4BO-0252X
• CCOE / PESO (India) Certificate: P333688
• NEPSI Certificate: GYJ13.1140X, GYJ13.1282X
• INMETRO Approval: TÜV 12.2073X
• RETIE Certificate: 03866
• RETIE Certificate: LRS: 01/00172, DNV: TAE00000Y, ABS: 14-LD234401A-4-PDA, BV: 43180/A1BV
• Ingress Protection Rating **: IP66, IP67 & IP68
• Deluge Protection Compliance: DTS01 : 91
• Cable Gland Material: Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
• Seal Material: CMP SOLO LSF Halogen Free Thermoset Elastomer / Epoxy Barrier Compound
• Cable Type: Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Wire Braid Armour (e.g. SWB), Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Strip Armour (e.g. ASA)***
• Armour Clamping: Detachable Compound Tube / Cone & AnyWay Universal Clamping Ring
• Sealing Technique: Unique CMP ‘LRS’ Outer Seal (Load Retention Seal)
• Sealing Area(s): Inner Compound Barrier & Outer Sheath
• Optional Accessories: Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds, Ingress Discs
• Optional Installation Tools: Spanners, Armour Former Tool
Globally Approved, Explosive Atmosphere Barrier Cable Gland:
• Metal-to-Metal Armour Clamping
• Direct & Remote Installation
• Compound Barrier Type Flameproof Seal
• Controlled Outer ‘Load Retention’ Seal
• Unique OSTG Prevents Overtightening
• Integral Protected Deluge Seal
• -60°C to +85°C
• Class I Zone 1, 21 and Zone 2, 22 Class I Division 1 & 2 ABCD
• Globally Marked, IECEx, ATEX, UL & cCSAus
• EMC Tested
Specification:
• Cable Gland Size: 20S16
• Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Standard Metric: M20
• Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Standard Thread Length (Metric) “E”: 15.0
• Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Standard NPT: ½”
• Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Standard Thread Length (NPT) “E”: 19.9
• Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Option NPT: ¾”
• Number of Cores: 11
• Diameter Over Conductors “A”: 11.7
• Cable Bedding Diameter “G” Max: 11.7
• Overall Cable Diameter “B” Min: 6.1
• Overall Cable Diameter “B” Max: 13.1
• Armour Range Grooved Cone (X) Min: 0.3
• Armour Range Grooved Cone (X) Max: 1.0
• Armour Range Stepped Cone (W) Min: 0.8
• Armour Range Stepped Cone (W) Max: 1.25
• Across Flats “D” Max: 30.5
• Across Corners “D” Max: 33.6
• Protrusion Length “F”: 62.0
• Combined Ordering Reference(*Brass Metric) Size: 20S16
• Combined Ordering Reference (*Brass Metric) Type: PX2K
• Combined Ordering Reference (*Brass Metric) Ordering Suffix: 1RA
• Shroud: PVC06
• Cable Gland Weight: 0.556 LBS