1/0-1/0-1/0-2 Copper SER Service Entrance Cable
Allowable Ampacity at 60° C: 125
Allowable Ampacity at 75° C: 150
Allowable Ampacity at 90° C: 170
Applications:
SER is a service entrance cable with a reinforcement tape used in all instances where service entrance cables are allowed. The electrical cable is most often used to connect the service drop to the meter base and from the meter base to the distribution panelboard. SER is suitable for dry locations, with temperatures not exceeding 90°C. The voltage rating the electrical cable is 600 volts.
Also Known As:
1/0-1/0-1/0-2 Copper SER Service Entrance Cable, 1/0-1/0-1/0-2 Reinforcement Tape Service Entrance Cable, 1/0-1/0-1/0-2 SER Cable, 1/0-1/0-1/0-2 SER Service Cable, 1/0-1/0-1/0-2 Copper Service Cable, 1/0-1/0-1/0-2 Round Service Entrance Cable.
Standards:
- ASTM- All applicable standards
- UL Standard 44 for XHHW-2 conductors
- UL Standard 83 for THHN/THWN conductors
- UL Standard 854
- Federal Specification A-A-59544
- National Electrical Code, NFPA 70. 2011 Edition
- RoHS/ REACH
Construction:
Conductor:
The cable is equipped with annealed soft copper conductors. It typically has three-phase conductors with a bare neutral.
Insulation:
The cable has cross-linked polyethylene type XHHW-2 insulation.
Jacket:
SE cable is jacketed with gray sunlight-resistant polyvinyl chloride (PVC). This dielectrically strong insulation is resistant to corrosion, abrasion, chemicals, and mechanical impact.
Specifications:
- Size AWG: 1/0-1/0-1/0-2
- Weight per 1,000 ft: 1382 lbs
- Outside Diameter: 1235 mils
- Conductors: Annealed Soft Copper
- Stranding: Phase & Neutral Conductors: 19
- Stranding: Equipment Ground Conductor: 19
- Insulation: XLPE
- Jacket: PVC
Compatible with Manufacturer |
|
Priority Wire & Cable : | 1/0-03CUG-R-SER |
Omni Cable : | 1/0-03GSERCU |
Southwire : | 27755802 |
[/short]
APPLICATIONS
Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. SER may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts.
SPECIFICATIONS
- ASTM- All applicable standards
- UL Standard 44 for XHHW-2 conductors
- UL Standard 83 for THHN/THWN conductors
- UL Standard 854
- Federal Specification A-A-59544
- National Electrical Code, NFPA 70. 2011 Edition
- RoHS/ REACH
CONSTRUCTION
Type cable is constructed with sunlight resistant Type XHHW-2 conductors or Type THHN/THWN conductors. Copper conductors are annealed (soft) copper. Cable assembly plus reinforcement tape are jacketed with sunlight resistant gray polyvinyl chloride (PVC). Available as 1 conductor with a concentric ground, 2 conductor with a round or concentric ground, or 3 conductor with a bare ground. SE cable is jacketed with gray sunlight resistant polyvinyl chloride (PVC).