250 MV105 Three Conductor Non-shielded EPR Insulation PVC Jacket Copper Power Cable 2.4kV
[short]
250 MV105 Three Conductor Non-shielded EPR Insulation PVC Jacket Copper Power Cable 2.4kV
Applications:
The mv105 copper cable is an electrical wire used for power circuits up to 2,400 Volts when fixed in open air, conduit, or duct; in applications such as chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations, and generating stations. The National Electric Code accepts this electrical cable for uses within 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Also Known As:
250 mcm medium voltage power cables, 250 mv power cable, 250 mv105 cable, 250 mv105,250 mcm mv power cable, 250 mcm mv105 cable, 250 mcm mv105.
Standards:
- ICEA S-93-639
- NEMA WC74
- AEIC CS8
- Federal Specification J-C-30B
Construction
Conductors:
The MV power cable conductor is made of copper, it is Class B stranding per ASTM B-8 (compressed), or ASTM B-496 (compact), with a semi-conducting conductor shield.
Insulation:
A strong and enduring ethylene-propylene rubber (EPR) is used as the insulation system. The good thing about this insulation is how friendly it is to human hands since it is a rubber, a material that tends to be soft but guarantees profound and reliable safety wires. This insulation is also environmentally friendly, it doesn’t have some toxics which can cause harm to human, animals, and plants health.
Jacket:
Reinforced insulation is provided by a PVC jacket, which is sunlight-resistant, per ICEA S-97-682 and UL Standard 1072.
Specifications:
- AWG Size: 250
- Number of strands: 37
- Overall diameter (inches): 1.14
- Net Weight (lb/1000FT): 1210
Compatible with Manufacturer |
|
Houston Wire & Cable : | HW21225003 |
[/short]
Power Cable
2.4kV UL Type MV-105, 105°C
Single Conductor, Non-Shielded
EPR Insulation, PVC Jacket
133% Insulation Level, Copper Conductor
Application:
Appropriate for all situations of corrosive environments in power circuits up to 2,400V in all installations of open air, conduit, and duct, cable tray when CT rated, in wet and dry locations. Main uses are for chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code permitted for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductor:
Has a semi-conducting conductor shield, with soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact). The ground conductor has a soft bare annealed compressed copper per ASTM B-3, and with stranding of Class B per ASTM B-8 sized in accordance to UL Standard 1072.
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682 with a semi-conducting insulation shield.
Jacket:
Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.
Standards:
- ICEA S-93-639
- NEMA WC74
- AEIC CS8
- Federal Specification J-C-30B